BECKHOFF EP3184-0002 ETHERCAT 4-CHANNEL ANALOG INPUT
EP3184-0002 | EtherCAT Box, 4-channel analog input, multi-function, ±10 V, 0/4…20 mA, 16 bit, single-ended, M12
BECKHOFF EP3184-0002. 4 Kanallı Analog Giriş Box (M12). 4 kanallı Analog Giriş Box. Çok fonksiyonlu (±10 V, 0/4...20 mA), 16 bit çözünürlüklü ve M12 konektörler kullanır. Saha ölçüm teknolojisinin kolay yapılandırılması için uygundur. EP3184-0002, 8 kanallı IP67 korumalı analog giriş terminalidir; proses kontrol ve ölçüm uygulamalarında kullanılır. Beckhoff EP3184-0002 – 8CH IP67 Analog Input EP3184-0002 | Beckhoff Analog Input Terminal IP67 8CH analog giriş. BECKHOFF EP3184-0002 ANALOG GIRIŞ (4–20MA), Beckhoff ep3184-0002 Analog Giriş (4–20mA), 4 kanal 4–20mA analog giriş modülü
|
Technical data |
EP3184-0002 |
|---|---|
|
Protocol |
EtherCAT |
|
Bus interface |
2 x M8 socket, 4-pin, a-coded, shielded |
|
Number of inputs |
4 (single-ended), 1 per socket |
|
Input connections |
M12 x 1, 5-pin, a-coded |
|
Conversion time |
~ 100 µs |
|
Resolution |
16 bit (incl. sign) |
|
Signal type |
-10/0…+10 V | 0/4…20 mA, parameterizable per channel |
|
Common-mode voltage UCM |
max. 35 V |
|
Internal resistance |
> 200 kΩ | typ. 85 Ω + diode voltage |
|
Measurement error/uncertainty |
< ±0.3% (relative to full scale value) |
|
Input filter limit frequency |
5 kHz |
|
Nominal voltage |
24 V DC (-15%/+20%) |
|
Distributed clocks |
yes |
|
Input filter |
configurable |
|
Sensor supply |
from load supply voltage UP |
|
Current consumption from US |
120 mA |
|
Power supply connection |
feed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded |
|
Electrical isolation |
500 V |
|
Special features |
current or voltage parameterizable |
|
Weight |
approx. 165 g |
|
Operating temperature |
-25…+60°C |
|
Storage temperature |
-40…+85°C |
|
Vibration/shock resistance |
conforms to EN 60068-2-6/EN 60068-2-27 |
|
EMC immunity/emission |
conforms to EN 61000-6-2/EN 61000-6-4 |
|
Protect. rating/installation pos. |
IP65/66/67 (conforms to EN 60529)/variable |
|
Approvals/markings |
CE, UL, ATEX, IECEx |
|
Ex marking |
ATEX: |
Anlaşmalı kargo, kurye seçenekleri mevcuttur. Otogar kargoları ile acil durumlarda gönderim yapılır. Ürünleri İzmir ve Kocaeli şubelerinden de teslim alabilirsiniz.