BECKHOFF BK5150 PLC
BK5150 | CANopen Compact Bus Coupler
| Technical data | BK5150 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 16 Tx/Rx PDOs |
| Number of PDOs (CANopen) | 16 Tx/Rx PDOs |
| Additional CANopen features | life, node guarding, emergency object, variable mapping, store/restore |
| Data transfer rates | automatic detection up to 1 Mbaud |
| Bus interface | open style connector, 5-pin |
| Data transfer medium | screened, twisted copper cable, 2 x signal, 1 x ground (recommended) |
| Power supply | 24 V DC (-15%/+20%) |
| Interfaces | configuration interface |
| Diagnostics LED | 2 x power supply, 2 x K-bus, 2 x fieldbus |
| Current supply K-bus | 1750 mA |
| Operating modes | synchron, cyclic, event driven, polling |
| Weight | approx. 100 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |