Skip to product information
BECKHOFF BK5220 PLC
BK5220 | DeviceNet Bus Coupler
| Technical data | BK5220 |
|---|---|
| Number of Bus Terminals | 64 (255 with K-bus extension) |
| Max. number of bytes fieldbus | 512 byte input and 512 byte output |
| Digital peripheral signals | 1,020 inputs/outputs |
| Analog peripheral signals | 256 inputs/outputs |
| Configuration | via KS2000 or the controller |
| Data transfer rates | automatic detection |
| Bus interface | 1 x open pluggable connector, 5-pin, included |
| Data transfer medium | screened, twisted copper wire with power supply, 5-pin |
| Power supply | 24 V DC (-15%/+20%), through bus cable 11…25 V (conforms to DeviceNet® specification) |
| Input current | 70 mA + (total K-bus current)/4, 500 mA max. |
| Starting current | approx. 2.5 x continuous current |
| Recommended fuse | ≤ 10 A |
| Current supply K-bus | 1750 mA |
| Power contacts | max. 24 V DC/max. 10 A |
| Electrical isolation | 500 V (power contact/supply voltage Bus Coupler) |
| Operating modes | bit strobe, polling, cyclic, change of state (COS) |
| Type | communications adapter |
| Weight | approx. 130 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, UL, ATEX, IECEx, DNV |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |
Contracted cargo and courier options are available. Shipments are made in urgent cases with bus station cargo. You can also pick up the products from Izmir and Kocaeli branches.